A 4567C • 10 Zone Line Monitoring Unit

Specifically designed to monitor the condition of 100V line speaker systems in emergency paging and fire evacuation installations. Traditional line monitoring units were limited to 50W per zone and would not handle this load. The A 4567B can handle loads up to 500W per zone.

SKU: A 4567C Categories: ,
Overview

Specifically designed to monitor the condition of 100V line speaker systems in emergency paging and fire evacuation installations. Many large commercial installations have speaker circuits in excess of 250W. Traditional line monitoring units were limited to 50W per zone and would not handle this load. The A 4567B can handle loads up to 500W per zone.

The microprocessor controlled circuit continuously monitors loudspeaker lines for normal, open or short circuit condition. A multi-colour LED indicates line condition accordingly for each zone. Internal audible alarm buzzer with cancel button is fitted. With any fault condition, a switched output is provided for remote monitoring purposes. This is a switched to ground signal.

Three outputs are supplied. One for short circuit conditions. One for an open circuit fault. Plus a combined output for any fault condition. The system can be configured to operate with multiple amplifiers. Dimensions: 482 x 152 x 44mm.

Key Features:

  • 1U 19″ rack mount
  • Monitors 10 zones @ 500W max
  • Configurable for use with 1 to 10 individual amplifiers. ie 1 amplifier per zone/circuit or 1 amplifier per many zones/circuits.
  • Monitors normal, open and short circuit conditions
  • Switched output for remote fault monitoring
  • Pluggable terminals for all connections
  • 24V dc operation (power supply included)

 

Wiring Requirements.

This unit is designed for “loop in loop out” serial wiring to loudspeakers with a 100kΩ terminating resistor at the end of the line. Star wiring or tee offs are prohibited. Each loudspeaker requires a series connected 22µf bipolar capacitor for correct operation. A delay of 10 seconds is provided before registering a fault to minimise false alarms.

A 4568 Zone Status Interface Option.

With the addition of the A 4568 you are able to monitor the status of each individual zone. The interface can be set up to monitor each zone in two ways. 1. LED status indicates normal or fault (no distinction between open or short). 2. LED status indicates either short or open. Connection between the A 4567B and A 4568 is via a Cat 5e patch lead. Screw terminals are provided for each zone.

 



Developed, designed & assembled in Australia.
Since 1974 Redback PA products have been manufactured in Perth, Western Australia by Altronics. With over 50 years experience in the commercial audio industry, we offer consultants, installers and end users reliable products of high build quality with local product support.



Backed by an industry leading 10 Year Manufacturer Warranty.
Our Redback products have a long tried and tested history of bulletproof reliability. Altronics offers a 10 Year Warranty on all Australian Made Redback products. Our local in-house service department has all the know how to answer technical queries and provide timely service.

Specifications
Electrical
Power handling: 500W per zone
Power requirements: 24V DC
Indicators: Tri-colour LED
Green – Normal, Orange – Open, Red – Short
Power outputs: Combined, open and short 24V DC
Inputs/outputs: 10 individual zones
Wiring configuration: Loop in, loop out

Controls
Buzzer cancel button
Power switch

Mechanical
Connections: Wire protect pluggable screw terminals
Dimensions: 482W x 152D x 44H mm
Weight: ≈3.5kg

Optional Accessories
A 4568 FIB interface module